Evacuating a refrigeration system means removing air and moisture from a new or repaired system before it is charged with refrigerant. If this step is skipped or done poorly, acid can form, the expansion valve can freeze and compressor life shortens. This article explains why evacuation matters and how to do it correctly.
Why evacuate?
Air left in the system collects in the condenser as non-condensable gas and raises discharge pressure. Moisture can combine with refrigerant and oil to form acid, and can freeze in the expansion valve and block it. Evacuation removes both enemies from the system.
For a proper vacuum
- Use a well-maintained vacuum pump sized for the job and change its oil regularly.
- Use hoses that are as wide and short as possible.
- Measure the vacuum with an electronic micron gauge, not the manifold gauge.
- After reaching the target, isolate the pump and do a standing test; if the reading rises quickly there is a leak or moisture.
Pressure test first
Before evacuation the system should be pressure tested with nitrogen. If there is a leak, the vacuum cannot be reached or the reading rises during the standing test. Refrigerant must not be charged until the leak is fixed.
Consequences of poor vacuum
High discharge pressure, low efficiency, valve blockage, oil breakdown and, in the long run, compressor failure. A few hours spent on evacuation prevent expensive failures later.
Frequently asked questions
How long should evacuation take?
Time is not what counts; the vacuum level reached and the standing test result decide.
Is nitrogen purging necessary?
Flowing nitrogen during brazing prevents oxide forming inside the pipes; nitrogen is also used for the pressure test.